Voltage drop calculator

Voltage lost along a cable run, from its length, cross-section and material.

Inputs

Voltage drop calculator

6 fields

Check the measurement units shown in or near the field.

Resistive estimate at 20 °C and power factor 1, not code-compliant cable selection. The adopted resistivities are model coefficients, not a product-specific resistance table.

Fill in the fields and the result will appear here automatically.

Compare voltage losses as cable length, cross-section or material changes. This is a resistive model: both conductors are counted for a two-wire single-phase circuit; balanced three-phase uses line-to-line voltage. Current is per conductor, displayed resistance is for one conductor on the one-way run, and power loss totals the current-carrying conductors. Reactance, imbalance, heating and contact resistance are not calculated.

FAQ
5 questions
Freshness
formula-based

How it works

Formula and logic

Rc = ρL/S with adopted 20 °C model coefficients: copper 0.0175 and aluminium 0.0282 Ω·mm²/m. ΔU = 2IRc for two wires; ΔU = √3IRc for balanced three-phase at power factor 1. Total heat loss is 2I²Rc or 3I²Rc respectively. Percentage = 100ΔU/U; load voltage = U − ΔU.

Example

Copper, 16 A, 20 m, 2.5 mm², 230 V: Rc = 0.0175 × 20/2.5 = 0.14 Ω; ΔU = 4.48 V = 1.95%; load voltage 225.52 V; loss 71.68 W. Aluminium, 32 A, 50 m, 6 mm², three-phase, 400 V: Rc = 0.235 Ω; ΔU = 13.025 V; total loss = 3 × 32² × 0.235 = 721.92 W.

Fields and units

  • Current — A
  • One-way run — m
  • Conductor cross-section — mm²
  • Conductor material — list option
  • Supply — list option
  • Nominal voltage — V

How to use

  • — Enter amperes and one-way length in metres; do not double the length yourself.
  • — Enter one conductor’s cross-section in mm², not its diameter, and choose copper or aluminium.
  • — Use voltage between the two wires for single-phase and between phases for three-phase, such as 400 V rather than 230 V.
  • — Zero current gives zero loss. If the drop exceeds nominal voltage, those inputs fall outside this supply model’s applicable range.

Method and limitations

Calculation method
Formula and logic
Limitation
Resistive estimate at 20 °C and power factor 1, not code-compliant cable selection. The adopted resistivities are model coefficients, not a product-specific resistance table.

FAQ

Why is three-phase loss not current times the voltage drop?

The drop √3IRc is line-to-line. Three conductors dissipate heat, giving 3I²Rc = √3IΔU. The voltage-drop factor √3 cannot replace the heating factor 3.

What does the displayed cable resistance mean?

It is one conductor’s resistance from source to load. A two-wire loop doubles it; three-phase has no single common loop resistance.

Can voltage-drop percentage alone select a cable?

No. Ampacity, protection, installation method and applicable local rules are also needed. This tool does not check them or set a regulatory limit.

Why can a warm cable differ from this result?

The coefficients are fixed at 20 °C. Actual cable temperature, tolerances and connections differ; operating temperature and reactive loads need a fuller model.

What changes if cross-section rises from 2.5 to 5 mm²?

At fixed current, length and material, R = ρL/S halves; voltage drop and I²R losses halve too. The 16 A, 20 m single-phase copper example becomes 2.24 V and 35.84 W instead of 4.48 V and 71.68 W. This comparison does not check ampacity.